12
E A S Y R E M O T E N O R D G A S
INSTALLER
played room temperature in order to
compensate any possible error.
P01 - Room anti-frost Start temper-
•
ature Range
It defines the start temperature for
the room anti frost function (0.1°C ÷
10°C).
N.B.: 0.0 = value 0.0 disables the room
anti frost function.
P02 - Differential operation temper-
•
ature OFF
It is the value to be added to the room
setpoint in order to define the end of the
Central Heating Demand.
Example:
T
set point
= 20.0 °C
P02 = 0.5 °C
T
set point
+ P02 = 20.0 + 0.5 = 20.5 °C
The central heating demand ends
whenever the room temperature is
higher then 20.5°C.
P03 - Differential operation temper-
•
ature ON
It is the value to be subtracted from the
room setpoint in order to define the start
of the Central Heating Demand.
Example:
T
set point
= 20.0 °C
P03 = 0.5 °C
T
set point
- P03 = 20.0 - 0.5 = 19.5 °C
The central heating demand starts
whenever the room temperature is
lower then 19.5°C.
P04 - Thermo-regulation type•
0 = ON/OFF
1 = Modulating on Room Temperature
sensor
2 = Modulating on External Temper-
ature Sensor (Outside Temperature
Compensation)
3 = Modulating on Room and External
Temperature sensors
4 = Disabled