Supply by communication bus
Number of temperature levels 2 (DAY / NIGHT)
Temperature setting range DAY 5 ÷ 30 °C
Temperature setting range NIGHT 5 ÷ 30 °C
Temperature setting range MANUAL 5 ÷ 30 °C
Differential operation temperature OFF 0.0 ÷ 1.0 °C
Differential operation temperature ON -1.0 ÷ -0.1 °C
Correct working range room temperature probe -40 ÷ 50 °C
Temperature resolution 0.1 °C
Room anti-frost start temperature range 0.1 ÷ 10.0 °C
Room anti-frost end temperature start value + 0.6 °C
Timer programmer resolution 30 minutes
Maximum number of startings and shutdowns per day 48
Number of standard heating programs 1
Number of standard storage tank programs 1
Internal clock time retention in case of power loss 1 hour
Operating temperature range 0 ÷ 50 °C
Stocking ambient temperature -10 ÷ 50 °C
Size (L×H×D) 118×85×30 mm
Maximum cable length for boiler connection 50 mt
Cable section for boiler connection 0,5 ÷ 1,5 mm
2
Technical features