EasyManua.ls Logo

Notifier AFP-200 - Appendix K - UL POWER-LIMITED WIRING REQUIREMENTS

Notifier AFP-200
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AFP-200 Instruction PN 15511:F2 10/11/99 113
Appendix K  UL Power-limited Wiring
Requirements
Figure K-1  Typical Wiring Diagram for UL Power-limited Requirements
AC Power
0.25" gap
0.75" gap
Nonpower-limited Circuits
Power-limited Circuits
Power-limited Circuits
General Description
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least ¼ inch away from any nonpower-limited circuit wiring. Furthermore, all
power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts
and/or conduits. A typical wiring diagram for the AFP-200 is shown in Figure K-1.
RTM-8 Relay Transmitter Module
Refer to Figure 2-35 for additional information on this module. Figure K-1 below shows the RTM-8 Module
installed in the AFP-200. Power-limited and nonpower-limited wiring must maintain a minimum distance of ¼
inch wire to wire. Note that a gap of ¾ inch exists between relay four and relay five. It is recommended that if
using this module to drive both power-limited and nonpower-limited circuits, use the first four relays to drive
power-limited circuits and the next four relays to drive nonpower-limited circuits. Using relays 5-8 for non-
power-limited circuits allows grouping them with the transmitter output nonpower-limited wiring.
If using all relays as power-limited circuits, the .25 inch gap between relay eight and the nonpower-limited
transmitter output terminal meets UL power-limited wiring requirements.

Other manuals for Notifier AFP-200

Related product manuals