EasyManua.ls Logo

Notifier AFP-200 - 2.7 Wiring the Signaling Line Circuit; 2.6 Remote Printers;Crt; The Isolator Module

Notifier AFP-200
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AFP-200 Instruction PN 15511:F2 10/11/99 31
Operation
By “flanking” each communications loop device with a pair of ISO-X isolator modules, each device is protected
from short circuit faults that may occur on other devices. For example, a fault on Zone 2 will not affect Zones 1
and 3. The isolator modules on either side of Zone 2 will open the communications loop. Zone 1 will still
operate from power on loop out and Zone 3 will operate from loop return. Because the control panel will no
longer be able to communicate with Zone 2, a trouble signal(s) will be generated for that device.
No T–tapping or branching is allowed on this circuit. The ratings and characteristics are the same as for a four-
wire circuit meeting NFPA Style 6 requirements.
Figure 2-16 Four Wire SLC Communications Loop
(meets NFPA 72-1993 Style 7 requirements)
Connect Loop Out to TB 6-3 (+) and TB 6-5 ().
Connect Loop Return to TB 6-4 (+) and TB 6-6 ().
2.7 Wiring the Signaling Line Circuit, continued

Other manuals for Notifier AFP-200

Related product manuals