Selecting AMG Tones and Messages 5. Voice Alarm Systems
AFP-300/AFP-400 Operations PN 50260:C1 05/22/97 29
AMG-1 and AMG-E Tone/Message Selections (AMG-1 SW2=Off) Table 23 lists
the tone and message selections available when SW2 rocker switch 2 (Tone/Message
Switch) is Off.
Table 23 Setting AMG Tones and Messages (AMG-1 SW2=Off)
1. MPS-400 Notification Appliance Circuit 1 (NAC1) can be manually selected with
an ACM 16AT to produce a desired tone or can be activated through Control-by-
Event by a non-alarm input.
2. If selecting a VROM or VRAM, and a VROM or VRAM chip is not installed, a
trouble indication appears at the AMG-1 when the message is due to begin and the
AMG-1 generates the 1 kHz default tone.
AMG-1 SW2 Rocker
Switches
System
Status
NAC 1 (B01)
Condition
Audio Tone or Message
S6 S7 S8
X X X No Alarm Off Standby
Off
Off
Off
Off
Off
Off
No Alarm
Alarm
On
X
1000 Hz 0.5 sec on, 0.5 sec off
Slow whoop
Off
Off
Off
Off
On
On
No Alarm
Alarm
On
X
Horn
120 ppm (March Time)
Off
Off
On
On
Off
Off
No Alarm
Alarm
On
X
Horn
Yelp
Off
Off
On
On
On
On
No Alarm
Alarm
On
X
Yelp
Wail
On
On
Off
Off
Off
Off
No Alarm
Alarm
On
X
3 slow whoops, VRAM-B plays
3 slow whoops, VRAM-A plays
On
On
Off
Off
O
On
No Alarm
Alarm
On
X
VROM-B message plays VROM-A
message plays
On
On
On
On
Off
Off
No Alarm
Alarm
On
X
20 ppm (Two-Stage) VROM-A and
VROM-B play
On
On
On
On
On
On
No Alarm
Alarm
On
X
Horn
NFPA Uniform Code 3
Temporal pattern fast whoop
X = Indicates that switch or control point can be On or Off.