4-11
Security 15088:K 03/21/01
MM Security Access Monitor:
Address: LXXMYY (Installer specified).
Type ID: SACM
Control-By-Event: (Za*)
Custom Label: Installer Option (describe specific
location of module).
Tracking: Yes - Each unsecured state and
restoral will be printed when the
print option is enabled.
No - the first unsecured state will
be printed when the print option is
enabled (restorals will not print un-
til reset at Central Station - short
condition only).
Annunciator: No (Not required).
Yes (if annunciator mapping de-
sired)
Annunciator Point
Mapping (Optional): AxxPyy
*'a' is an installer specified num-
ber. In this example, all modules
must be assigned the same zone
number.
B: MM programming:
Address: LXXMYY (Installer specified).
Type ID: SARM
Control-By-Event: ( )
Custom Label: Installer Option (describe location
of module).
Tracking: Yes - Results in required acknowl-
edgment at Central Station for ev-
ery unsecured state. Restoral is
automatic.
No - Results in required acknowl-
edgment at Central Station for first
unsecured state only (until reset at
Central Station - short condition
only).
Annunciator: No (Not required).
Yes (if annunciator mapping de-
sired)
Annunciator Point
Mapping (Optional): AxxPyy
Group Interface:
A: CM programming:
Address: LXXMYY (Installer specified).
Type ID: CMXC
Control-By-Event: (Za*)
Custom Label: Security Group Output
Signal Silence: No
Walk Test: Yes/No (Installer Specified).
Annunciator: No (Not required).
MM = CM
Programming Key for Figure 1.3-4