EasyManua.ls Logo

Notifier FCPS-24S8

Notifier FCPS-24S8
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applications Controlling Four NACs With One Input and Selective Silence
26 FCPS-24S PN 51977:C1 08/06/03
Notes: The following notes apply to Figure 5.1 on page 25.
1. When the FCPS-24S power supply is in an inactive state (control module not
active), a trouble on the power supply will result in an open circuit condition on
the control module output circuit (monitored by End-of-Line Resistor across
TB4, Terminals 5 & 6). As an alternative, the trouble contacts at TB5 of the
power supply can also be used for independent trouble monitoring.
2. The addressable relay module must be programmed as a silenceable point at the
FACP to allow selective silence of horn/strobe devices. The Normally Open
contact of the relay module is connected between TB4 Terminal 7 (IN2 +) and
Terminal 9 (Aux. Power +).
3. Do not loop wires under screw terminals. Break wires to maintain proper
supervision.
4. An End-of-Line Resistor must be installed between TB4, Terminals 5 & 6 for
control module wiring supervision (the ELR value is dependent on the module
employed).
5. Supervise the power wiring between the FPCS-24S auxiliary 24 VDC output on
TB4, Terminals 9 & 10 with an EOL relay (P/N: A77-716B)
6. For a list of compatible devices, refer to the Device Compatibility Document.
7. IMPORTANT! When the power supply is programmed for both Selective
Silence and Slave Mode, TB4 Terminal 7 (IN+) must be jumpered to Terminal 9
(AUX+) and Terminal 8 (IN-) must be jumpered to Terminal 10 (AUX-). The
FACP will control the Selective Silence feature with this configuration.
If the terminals are not jumpered as indicated, the horn portion of the horn/
strobes will be silenced
at all times.
TB4
1 2 3 4 5 6 7 8 9 10
SYNC SYNC IN+ IN- OUT+ OUT- IN2+ IN2- AUX+ AUX-
www.PDF-Zoo.com

Table of Contents

Related product manuals