System Overview Start-up Procedure
8 FCPS-24S PN 51977:C1 08/06/03
Maximum total short term current (one hour maximum):
6.0 amps for FCPS-24S6
8.0 amps for FCPS-24S8
Integral supervised battery charger for lead acid batteries only
Capable of charging 7.0 AH to 18.0 AH (Amp Hour) batteries
Fully supervised power supply, battery and NACs
Selectable Strobe Synchronization for NACs (System Sensor, Gentex
(Commander II) and Wheelock)
Coded signal synchronization
Fixed terminal blocks for field wiring capable of accepting 12 - 22 AWG wire
Selectable Ground Fault detection by jumper JP1
Power supply trouble Form-C relay contacts (fail-safe)
Optional delay of AC loss reporting for 8 hours
Auxiliary Power Output for SLC modules (500 mA maximum) with optional
reset for 4-wire smoke detectors
Mounting location for optional addressable control module
1.3 Start-up Procedure
1. Configure the power supply jumpers as described in "Jumpers" on page 9
2. Install the power supply as described in "Installation" on page 13
3. Program the power supply as described in "Programming Options" on page 18
4. Wire the power supply circuits, referring to the options described in "Trouble
Supervision" on page 23 and the application examples in "Applications" on page
25
5. Connect primary power source wiring while observing the following:
Make certain that the AC mains circuit breaker is off before making any
wiring connections between the mains and the power supply
Make certain primary power source is 120 VAC, 60 Hz, 3.2 amps
Run a pair of wires (with ground conductor) from the protected premises main
breaker box to TB1 of the power supply main circuit board
Use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V insulation
6. Apply power to the power supply using the following procedure:
connect a properly charged battery to connector JP4 on the power supply main
circuit board
apply AC power by turning on the AC mains circuit breaker connected to the
power supply
www.PDF-Zoo.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier FCPS-24S8 and is the answer not in the manual?

Notifier FCPS-24S8 Specifications

General IconGeneral
BrandNotifier
ModelFCPS-24S8
CategoryPower Supply
LanguageEnglish

Related product manuals