Software Type ID Codes Alphabetical List
60 NFS-3030 Operating P/N 51344:C 11/4/03
Appendix Table A-1 Software Type ID Codes, Alphabetical List
POWER MONITR Monitor for main and auxiliary power supplies
PULL STATION Manual fire-alarm activating device
REL AUDIBLE Activates audio or visual devices steady when releasing starts
REL END BELL Control module used to activate NAC audio or visual device when releasing circuits shut off
REL CKT ULC Control module used to direct outputs to perform a release function as required by ULC
RELAY Form-C relay control module
REL. FORM C Form-C relay that directs outputs to perform a releasing function
RELEASE CKT Directs outputs to perform a releasing function
RESET SWITCH Monitor used to reset the control panel
RF MON MODUL Wireless alarm-monitoring device
RF PULL STA Wireless manual fire alarm-activating device
RFSMOKE(PHOTO) Wireless smoke detector
RF SUPERVSRY Wireless supervisory-monitoring device
SECOND SHOT Monitor module that provides a second manual release for a releasing zone through
connection to a UL-listed pull station
SECURITY L Monitor for activation of latching security alarm
SIL SWITCH Monitor used as Signal Silence switch, turning off all activated silenceable outputs
SMOKE ACCLIM Combination photoelectric/heat detector
SMOKE(ACCLIM+) Combination photoelectric/heat detector with low temperature warning
SMOKE CONVEN Conventional smoke detector attached to an FZM-1
SMOKE DETECT Conventional smoke detector attached to an FZM-1
SMOKE(DUCTI) Duct ionization smoke detector
SMOKE(DUCTP) Duct photoelectric smoke detector
SMOKE(HARSH) HARSH smoke detector
SMOKE(ION) Ionization smoke detector
SMOKE(LASER) Laser smoke detector
SMOKE(MULTI) Multisensor smoke detector
SMOKE(PHOTO) Photoelectric smoke detector
SPEAKER Control module for speaker
SPRINKLR SYS Monitor for a waterflow device
STROBE Control module used with NAC with strobes
SUP L(DUCTI) Duct ionization smoke detector, latching
SUP L(DUCTP) Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, latching
SUP L(ION) Ionization smoke detector, latching
SUP L(PHOTO) Photoelectric smoke detector, latching
SUP T(DUCTI)* Duct ionization smoke detector, tracking
SUP T(DUCTP)* Photoelectric smoke detector used as a duct detector to report supervisory condition rather
than alarm, tracking
SUP T(ION)* Ionization smoke detector, tracking
SUP T(PHOTO)* Photoelectric smoke detector, tracking
SYS MONITOR Monitor for equipment security
TAMPER Monitor for activation of tamper switch
TELE PAGE Monitor used to emulate the page button on an FFT-7, allowing remote paging to a fire area
TELEPHONE Control module for standard telephone circuit
TRACKING SUPERV Monitor for waterflow tamper switches for alarm points
TROUBLE MON Monitor for trouble inputs
WATERFLOW Monitor for waterflow alarm switch
WATERFLOW S Monitor for supervisory condition for activated waterflow switch
*Not suitable for Canadian applications.
Software Type ID Code Device
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier NFS-3030/E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-3030/E and is the answer not in the manual?

Notifier NFS-3030/E Specifications

General IconGeneral
BrandNotifier
ModelNFS-3030/E
CategoryControl Panel
LanguageEnglish

Related product manuals