Installation and Service Manual
6
32-0002-r12_2018-09
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4.3.1. Enter Access Level 3
To enter the Access Level 3 passcode, take the following actions:
1) Press and hold the ACK button for 3 s. The A1 LED will flash rapidly.
2) Enter the Access Level 3 passcode using the DISABLEMENT buttons numbered 1 ~ 4. Each button press
will cause the following indicator to light:
First button press
B 1
Second button press
B 2
Third button press
B 3
Fourth button press
B 4
3) Press ACK button to confirm the passcode.
If the passcode is correct:
The internal sounder will give a double short beep.
The A3 LED will flash three times, pause, then repeat.
If the passcode is incorrect:
The internal sounder will give a single long beep.
The Zone indicators will turn off.
A new passcode can be entered.
To exit Access Level 3, press HOME, then the ACK button to confirm.
4.3.2. Change Access Level 3 Passcode
The Access Level 3 passcode may be changed from the factory default setting. The Access Level 3 passcode
cannot be the same as the Access Level 2 passcode.
To change the passcode, take the following actions:
1) Enter Access Level 3.
2) Press and hold the ACK button for 10 s. The A1 LED will flash rapidly.
3) Press the ALARM RELAY button. The ACK LED and the ALARM RELAY LED will both flash.
4) Press ACK button. The ACK LED will be off and the ALARM RELAY LED will illuminate.
5) Enter the new 4-digit Access Level 3 passcode using the DISABLEMENT buttons numbered 1 ~ 4. The
Access Level 3 passcode must be different to the Access Level 2 passcode. Each button press will cause
the following indicators to light:
First button press
B 1
Second button press
B 2
Third button press
B 3
Fourth button press
B 4
6) Press ACK button to confirm the passcode.
Note: The ACK LED does not flash during this process until the 4 passcode numbers are entered.
7) Repeat Steps 5 and 6 to confirm the passcode. The internal sounder will give a double short beep.
Passcode is now changed.
If the two passcodes entered are different:
The internal sounder will give a single long beep.
The Zone indicators will turn off.
A new passcode can be entered.
Access Level 3 can only be entered if there are no new events to acknowledge.
The factory default Access Level 3 passcode is 4321.