4001 non-addressable control and indicating equipment
Installation and Service Manual
1
32-0002-r12_2018-09
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information shown were current at the date of publication and subject to change without notice.
1. INTRODUCTION
1.1. Features
The 4001 includes features that provide a flexible solution for small and medium-sized buildings. The
equipment is easy to install and quick to configure and commission. A reliable microprocessor delivers trouble-
free operation, lowering service costs and increasing up-time. Features include:
2, 4 or 8 detection zones
Supports up to 32 non-addressable devices per alarm zone circuit
Configurable non-latching detection zones
Configurable alarm dependency (zone coincidence detection)
Capacitor end-of-line device
Configurable timer to delay output activation (up to 10 min)
3 Access Levels
Single-person test mode
Day/night mode configurable
Manual activation of alarm devices
Auxiliary DC 24 V output, with short-circuit protection
Programmable non-addressable alarm output circuit
2 unmonitored relay contacts for Fire Alarm Condition outputs
1 unmonitored relay contact for Fault Condition output
3 voltage-free inputs for remote reset, evacuation start/stop, and Day/Night mode
Clear detection zone LED indicators, with a single indicator for Fault, Disable and Test Condition
indicator
Recessed mounting enclosure
Supports up to 7 Repeater Panels
1.2. Factory Default Settings
The 4001 control and indicating equipment is supplied ready to operate. Optional functions and their
configuration are described in following sections.
The default settings for the 4001 are as follows:
Detection zones are latching
Delay timers are disabled
Alarm dependency (zone coincidence detection) is disabled
Access Level 2 passcode is set to 2244
Access Level 3 passcode is set to 4321
If used, non-latching Detection Zones do not comply with EN 54-2.
If used, alarm dependency (zone coincidence detection) does not comply with
EN 54-2.