4001 non-addressable control and indicating equipment
Installation and Service Manual
4
32-0002-r12_2018-09
© 2015 ~ 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information shown were current at the date of publication and subject to change without notice.
4. ACCESS LEVELS
Three access levels are used to operate or configure the control and indicating equipment.
4.1. Access Level 1
Access Level 1 provides open access to perform the following functions:
Acknowledge a new event (and silence the internal sounder).
Override any active delays in the Alarm Condition.
Perform the indicator test.
Place the panel into Access Level 2 or Access Level 3.
4.2. Access Level 2
Access Level 2 provides access to the following functions for authorized users:
Acknowledge a new event (and silence the internal sounder).
Override any active delays.
Perform the indicator test.
Silence and re-activate alarms (including for a building evacuation).
Reset the fire detection and alarm system.
Disable or enable the following:
o Zones
o Alarms
o Auxiliary outputs
Activate delays (if configured).
4.2.1. Enter Access Level 2
To enter the Access Level 2 passcode, take the following actions:
1) Press and hold the ACK button for 3 s. The A1 LED will flash.
2) Enter the Access Level 2 passcode using the DISABLEMENT buttons numbered 1 ~ 4. Each button press
will cause the following indicator to light:
First button press
B 1
Second button press
B 2
Third button press
B 3
Fourth button press
B 4
3) Press the ACK button to confirm the passcode.
If the passcode is correct:
The internal sounder will give a double short beep.
The A2 LED will flash twice, pause, then repeat.
If the passcode is incorrect:
The internal sounder will give a single long beep.
Indicators B 1 ~ B 4 will turn off.
A new passcode can be entered.
To exit Access Level 2, press HOME, then the ACK button to confirm.
Access Level 2 can only be entered if there are no new events to acknowledge.
The factory default Access Level 2 passcode is 2244.