Wiring the AcquiSuite Ally Meter in a 4-wire, 3 ɸ Service Panel
Illustrating the intended wiring configuration for each of the Service Types
available in the Service drop-down list under “Meter Setup”
Note: The AcquiSuite Ally Meter Series uses the “Neutral” Terminal as a voltage reference.
For systems without a neutral conductor, Obvius suggests connecting a ground wire to this
terminal. If the neutral terminal is left open, L-L measurements will be accurate, but L-N
measurements may not be symmetric. If a ground wire is connected to the Neutral terminal,
<2mA will flow into the ground wire.
Connect the
Neutral wire
or Ground wire to
V INPUT 1 (N) on
the meter
Meter Power
Connect all phases
to the V INPUT 1
terminal
(Label as Disconnect)
3-Wire, 3 ɸ
DELTA load
(No possibility of
Neutral Current)
L1-N, L2-N(est), L3-N
3 Wire, 3 ɸ used
On MAINS
L1-N, L2-N, L3-N
(Rogowski Coils Shown)
Single Phase
Branch Loads
L1-N
4 Wire, 3 ɸ
WYE load
(Neutral Current)
L1-N, L2-N, L3-N