5. Quick Parameter List
*1
*1 Refer to user’s manual for complete list
Parameter No. Description Range Default
n01 Parameter access:
0: Limited parameter access
1: Full parameter access
8: Factory parameter initialise
0 to 9 1
n02 Run command selection:
0: Digital operator
1: Control circuit terminal
2: Communication (option)
0 to 2 0
n03 Frequency reference selection:
0: Digital operator (potentiometer)
1: Frequency reference 1 (n21)
2: Control circuit terminal (0 to 10V)
3: Control circuit terminal (4 to 20mA)
4: Control circuit terminal (0 to 20mA)
6: Communication (option)
0 to 4, 6 0
n09 Maximum output frequency 50 to 400Hz
n10 Maximum output voltage 1 to 255V (200V class)
1 to 510V (400V class)
200 (200V class)
400 (400V class)
N11 Maximum voltage output frequency 50 to 400Hz
n16 Acceleration time 1 0.0 to 999sec 10sec
n17 Deceleration time 2 0.0 to 999sec 10sec
n21 Frequency reference 1 0.0 to 400Hz 50Hz
n22 - n28 Frequency reference 2 - 8 0.0 to 400Hz 0Hz
n32 Motor rated current Depending on model 0 to 120% of inverter rated
output current
n36 - n39 Multi-function input (S2 -S5) 0 to 35 --
n40 Multi-function output (MA-MB-MC) 0 to 18 1
n44 Multi-function analog output (AM-AC):
0: Output frequency (10V/Max, freq.)
1: Output current (10V/Inverter rated current)
0,1 0
n46 Carrier frequency 1 to 4 (2.5 - 10kHz)
7 to 9 (Proportional to
output freq.)
Depending on model
n52 DC injection braking current 0 to 100% 50%
n53 DC injection braking at stop 0 to 100% 50%
n54 DC injection braking at start 0 to 100% 50%
n55 Stall prevention during deceleration:
0: Enabled
1: Disabled
0,1 0
Multi-function Inputs Multi-function Outputs
Value
*1
Function Value
*1
Function
2 Reverse/Stop 0 Fault Output
3 External Fault (NO) 1 During Run
4 External Fault (NC) 2 Frequency agree
5 Faul reset 6 Overtorque being monitored (NO)
6 Multi-step speed reference 1 12 RUN mode
7 Multi-step speed reference 2 13 Inverter ready