212
Manipulating Files Section 5-2
Example Program 1
Store program files ABC.OBJ and XYZ.OBJ in the Memory Card and select
one program or the other depending upon the value of D00000. Set D00000
to #1234 when selecting ABC.OBJ or set it to #5678 when selecting
XYZ.OBJ.
Replacement Start Bit
(Not supported by CS-series
pre-EV1 CS1 CPU Units)
A65015 If this bit has been enabled by the setting the Program Password (A651)
to A5A5 Hex, program replacement will start when this bit is turned from
OFF to ON. Do not turn this bit from OFF to ON again during program
replacement.
This bit is automatically turned OFF when program replacement is com-
pleted (normally or with an error) or the power is turned ON.
The status of this bit can be read from a Programming Device, PT, or host
computer to determine whether program replacement has been com-
pleted or not.
Program Password
(Not supported by CS-series
pre-EV1 CS1 CPU Units)
A651 Write the password to this word to enable program replacement.
A5A5 Hex: Enables the Replacement Start Bit (A65015).
Other value: Disables the Replacement Start Bit (A65015).
This bit is automatically turned OFF when program replacement is com-
pleted (normally or with an error) or the power is turned ON.
Program File Name
(Not supported by CS-series
pre-EV1 CS1 CPU Units)
A654 to
A657
Name Address Operation
Before starting program replacement, write the file name of the
replacement program file in these words in ASCII. Just write the
8-character filename; the .OBJ extension is added automatically.
Write the characters in order from A654 (most significant byte first). If
the file name has fewer than 8 characters, pad the remaining bytes with
space codes (20 Hex). Do not include any NULL characters or spaces
within the file name itself.
The following example shows the data for the program file ABC.OBJ:

Table of Contents

Other manuals for Omron CJ1M-CPU series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ1M-CPU series and is the answer not in the manual?

Omron CJ1M-CPU series Specifications

General IconGeneral
BrandOmron
ModelCJ1M-CPU series
CategoryController
LanguageEnglish

Related product manuals