13 Troubleshooting
13-34
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
84E10000 hex BOOTP
Server Error
Connection with the
BOOTP server
failed.
Server setting error (The
acquired IP address is illegal.)
Server is down.
An error occurred in the com-
munications path.
S page 13-46
54AF0000 hex Access
Detected
Outside
Range of
Variable
Accessing a value
that is out of range
was detected for a
tag variable that is
used in a tag data
link.
An out-of-range value was writ-
ten by an EtherNet/IP tag data
link for a variable with a speci-
fied range. A value that does
not specify an enumerator was
written by an EtherNet/IP tag
data link for an enumeration
variable.
S page 13-46
84E20000 hex Link OFF
Error
The Ethernet link
status turned OFF.
The Ethernet cable is discon-
nected.
An Ethernet cable is discon-
nected or loose.
The switching hub power sup-
ply is turned OFF.
Baud rate mismatch.
Noise
U S page 13-47
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info