E5jJ
E5jJ
E5AJ/E5BJ/E5EJ
Output value
Press a
o
(Output value display)
20
Press a
cp
1.0
Press a
hys
0
Press a
spĆ0
Press a
sPĆ1
Press a
ct
0.0
Press a
hb
8.0
Press a
p
233
Press a
i
40
Press a
d
50.0
Press a
ofr
ON/OFF
control
(Hysteresis
setting)
PID control
(Control period setting)
(Models with event input)
(Set point 0 setting SP0)
(Set point 1 setting SP1)
If control output is
current output.
(Heater current
value display)
(Heater burnout
alarm value setting)
If the control mode is set to
2-PID
(Proportional band setting)
(Integral time setting)
(Derivative time setting)
(Manual reset
value setting)
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
0
Current
value
(see note)
When I = 0
1234
O
N
1234
O
N
1234
O
N
(See note)
Without heater
burnout alarm
(See note)
Note: Nothing
is displayed in current output model.
Output V
alue Display:
o
Displayed range 0.0% to 100.0%
Control Period: cp
The
control period can be set with the Down and Up Keys within a
range
of 1 to 99 s. The control period is factory-set to 20 s.
In
the case of 2-PID, the relay output or voltage
output repeats turn
-
ing ON and OFF, the cycle of which is
called a control period. The
duration that the output is ON is in proportion to the output value.
The
shorter
the control period is, the smoother the control operation
will be. If the control period
is, however
, too short, the life of the relay
will
be shortened. Therefore the control period should be 20 s mini
-
mum
in the case of relay output.
ON
OFF
Control period:
10 seconds
ON
OFF
Control period:
20 seconds
Output
V
alue: 50.0%
Hysteresis:
hys
The
hysteresis value for the ON/OFF control can be set in a range
from 0.0
°
to 999.9
°C/°
F while “
hys
” is displayed on the PV
display
using
the Up and Down Keys. The value is factory-set to
1.0
°C/°F.
However,
the E5
j
J-F (Fahrenheit Model) is factory-set to 1.8
°F.
Low temperature set point High temperature
Hysteresis
ON
OFF
Reverse operation
(heating control)
Hysteresis
ON
OFF
Normal operation
(cooling control)
Low temperature set point High temperature
Set
Point 0 Setting (
°C or °F): spĆ0
Use
the Down and Up Keys to set the set point 0. It is possible to set
the
value
regardless of whether the set value presently selected is
on
SP0 or SP1.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5 J Series and is the answer not in the manual?

Omron E5 J Series Specifications

General IconGeneral
BrandOmron
ModelE5 J Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals