EasyManua.ls Logo

Omron E5 J Series - Alarm Configuration Options; Alarm Mode Selector Functions; Deviation vs. Absolute Alarms

Omron E5 J Series
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E5jJ
E5jJ
9
Alarm Mode Selectors (ALM1, ALM2)
Alarm
modes, listed
in the following table, can be selected using this switch. The switch is factory-set to position 2, i.e., the upper-limit alarm
mode.
Switch Mode Alarm output
Setting range
setting
Alarm operation
When X is positive
When X is negative
0
No alarm
OFF ---
1 Upper- and lower-limit alarm
(deviation)
XX
ON
OFF
SP
Always ON –1999
to 9999, or –199.9 to 999.9
(The decimal position varies with
the
input type.)
2
Upper-limit alarm (deviation)
X
SP
X
SP
3
Lower-limit alarm (deviation)
X
SP
X
SP
4 Upper- and lower-limit alarm
(deviation)
XX
SP
Always OFF
5 Upper- and lower-limit alarm with
standby
sequence (deviation)
XX
SP
Always OFF
6
Upper-limit alarm with standby
sequence (deviation)
X
SP
X
SP
7
Lower-limit alarm with standby
sequence (deviation)
X
SP
X
SP
8
Absolute-value upper-limit alarm
0°C/°F
X
0°C/°F
X
9
Absolute-value lower-limit alarm
0°C/°F
X
0°C/°F
X
Deviation Alarm
If
the alarm mode selector is set to a number between 1 to 7, alarm
values
are set to the width deviated from the set point as shown in
the
following illustration.
Set point (SP)
100°C/°F
Alarm value
10°C/°F
110°C/°F
Absolute Alarm
If
the alarm mode selector is set to 8 or 9, alarm values are set to the
absolute
value based on 0
°C/°
F as shown in the following illustra
-
tion.
0°C/°F
Alarm value
110°C/°F
110°C/°F

Related product manuals