Advanced Function Setting Level Section 5-7
Related Parameters
SP 0 to SP 3 (adjustment level): Page 111
Event input assignment 1, Event input a
ssignment 2, Multi-SP uses: Page
132
(advanced function setting level)
• The following functions are assigned for event input 1 and event input 2.
RUN/STOP
Auto/manual switch
• Defaults:Event input assignment 1: none
Event input assignment 2: stop
Related Parameters
SP 0 to SP 3 (adjustment level): Page 111,
Number of multi-SP uses (advanced function setting level): Page 131
This parameter enables switching between set points 0 to 3 by operating the
keys on the front panel.
Prerequisites
• A model without event inputs
• The “number of multi-SP uses” parameter set to 0 on a model with event
inputs
on: Set points 0 to 3 can be selected.
off: Set points 0 to 3 cannot be selected.
• Default : OFF
Related Parameters
Multi-SP set point setting (operation level): Page 99
Number of multi-SP uses (advanced function setting level): Page 131
• This parameter sets the time unit for the rate of change during SP ramp
operation.
See
See
ev-1 Event Input Assignment 1
Event inputs must be supported.
The “number of multi-SP uses”
parameter must be set to 0 or 1.
ev-2 Event Input Assignment 2
Settings Function
none None
stop RUN/STOP
manu Auto/manual switch
Function
Setting
See
See
mspu Multi-SP Uses
The model must not support event
inputs, or the number of multi-SP
uses must be 0.
Function
Setting
See
See
spru SP Ramp Time Unit
The “ST” parameter must be set to
OFF.
Function
■
■
■