E5@C-T Digital Temperature Controllers User’s Manual (H185)
5-18 Setting the Width of MV Variation
5
5-18-1 MV Change Rate Limit
This procedure sets the MV change rate limit to 5.0%/s. The related
parameters are as follows:
PID ON/OFF = PID
Operating Procedure
• Setting 2-PID Control
1
Press the M Key several times in the Initial Setting Level to
display cntl (PID ON/OFF).
Initial Setting Level
2
Press the U or D Key to select pid (PID).
The default is pid (PID control).
• Setting the MV Change Rate Limit
1
Press the M Key several times in the Adjustment Level to dis-
play orl (MV Change Rate Limit).
Adjustment Level
2
Press the U or D Key to set the value to 5.0.
The default is 0.0 (%/s).
pid
cntl
PID ON/OFF
pid
cntl
0.0
orl
MV Change
Rate Limit
5.0
orl