6 - 57
6 Parameters
E5@C-T Digital Temperature Controllers User’s Manual (H185)
6-9 Initial Setting Level
6
in-h
Scaling Upper Limit
The input type must be set for an analog input.
in-l
Scaling Lower limit
dp
Decimal Point
The Decimal Point parameter specifies the decimal point position of parameters (set
point, etc.) whose unit is EU.
Scaling Upper Limit, Scaling Lower Limit
Decimal Point
z Related Parameters
Input Type (Initial Setting Level): Page 6-56
d-u
Temperature Unit The input type must be set for a temperature input.
Set the temperature input unit to either °C or °F.
z Related Parameters
Input Type (Initial Setting Level): Page 6-56
Function
Setting
Parameter name Setting range Default
Scaling Upper Limit Scaling lower limit + 1 to 9999 100
Scaling Lower Limit 1999 to scaling upper limit 10
Parameter name Setting range Default
Decimal Point 0 to 3 0
Set value Settings Example
0 0 digits past decimal point 1234
1 1 digits past decimal point 123.4
2 2 digits past decimal point 12.34
3 3 digits past decimal point 1.234
See
See
Function
Setting
Setting range Default
c: °C, f: °F c