6 Parameters
6 - 88
E5@C-T Digital Temperature Controllers User’s Manual (H185)
mav
Moving Average Count
• This parameter sets the number of inputs to include in the moving average. The data after
moving average processing is illustrated in the following figure.
• Use a moving average to suppress rapid changes in the input.
ret
Automatic Display Return Time
• In the Operation Level, Program Setting Level, Adjustment Level, PID Setting Level, or
Monitor/Setting Item Level, the display automatically returns to the PV/SP if there are no
key operations for the time set for this parameter.
• The automatic display return time is disabled when the parameter is set to OFF. (In that
case, the display will not be automatically switched.)
brgt
Display Brightness
This parameter sets the display brightness to one of three levels. Adjust the level if the dis-
play is too bright.
Function
Input data
Operation result
Time
Setting
Setting range Unit Default
OFF, 2, 4, 8, 16, 32 Times OFF
Function
Setting
Setting range Unit Default
OFF, 1 to 99 Seconds off
Function
Setting
Setting range Default
1 (dark) to 3 (bright) 3