EasyManuals Logo

Omron E5CC-T User Manual

Omron E5CC-T
438 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #403 background imageLoading...
Page #403 background image
A Appendices
A - 14
E5@C-T Digital Temperature Controllers User’s Manual (H185)
z Meaning
“----” will be displayed for the Valve Opening Monitor parameter if any of the following error occurs.
Motor calibration has not been performed.
The wiring of the potentiometer is incorrect or broken.
The potentiometer input value is incorrect (e.g., the input is out of range or the potentiometer has
failed).
z Action
Check for the above errors.
z Operation
Close control: The control output is OFF or the value that is set for the MV at PV Error parameter is
output.
Floating control: Operation will be normal.
----
Potentiometer Input Error (Position-proportional Models Only)

Table of Contents

Other manuals for Omron E5CC-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC-T and is the answer not in the manual?

Omron E5CC-T Specifications

General IconGeneral
BrandOmron
ModelE5CC-T
CategoryTemperature Controller
LanguageEnglish

Related product manuals