E5CK-T E5CK-T
181
J AFTER TURNING POWER ON
Determine the I/O specifications of the Process Controller in setup
mode.
Power ON
Process value
1 s min.
1 s min.
Input type
Temperature input Current/Voltage input
°C/°F
selection
Scaling
upper limit
Scaling
lower limit
Decimal point
Parameter initialize
From next page To next page
prgn
J INPUT TYPE
Set the code according to the following table. Default is
2: K1 thermocouple.
Platinum Resistance Thermometer
Set Input typeSet
value
Input type
0 JPt100 199.9 to 650.0 (°C)
/199.9 to 999.9 (°F)
Platinum
resistance
1 Pt100 199.9 to 650.0 (°C)
/199.9 to 999.9 (°F)
thermometer
2 K1 200 to 1,300 (°C)
/300 to 2,300 (°F)
Thermocouple
3 K2 0.0 to 500.0 (°C)
/0.0 to 900.0 (°F)
4 J1 100 to 850 (°C)
/100 to 1,500 (°F)
5 J2 0.0 to 400.0 (°C)
/0.0 to 750.0 (°F)
6 T 199.9 to 400.0 (°C)
/199.9 to 700.0 (°F)
7 E 0 to 600 (°C)
/0 to 1,100 (°F)
8 L1 100 to 850 (°C)
/100 to 1,500 (°F)
9 L2 0.0 to 400.0 (°C)
/0.0 to 750.0 (°F)
10 U 199.9 to 400.0 (°C)
/199.9 to 700.0 (°F)
11 N 200 to 1,300 (°C)
/300 to 2,300 (°F)
12 R 0 to 1,700 (°C)
/0 to 3,000 (°F)
13 S 0 to 1,700 (°C)
/0 to 3,000 (°F)
14 B 100 to 1,800 (°C)
/300 to 3,200 (°F)
15 W 0 to 2,300 (°C)
/0 to 4,100 (°F)
16 PLII 0 to 1,300 (°C)
/0 to 2,300 (°F)
17 4 to 20 mA Current input
18 0 to 20 mA
19 1 to 5 V Voltage input
20 0 to 5 V
21 0 to 10 V