112
Adjustment Level Section 5-4
These parameters are used to shift the input temperature at two points: an
upper-limit temperature and a lower-limit temperature (as opposed to the
“temperature input shift” parameter, which shifts the input temperature by set-
ting the shift for only one point). A 2-point shift enables more accurate offset
of the input range compared with a 1-point shift if the input shift values at the
upper and lower limits differ.
This parameter sets input shift values for the upper and lower limits (2-point
shift) of the input range.
Related Parameters
Input type (initial setting level): Page 119
Input shift type (advanced function setting level): Page 142
insh Upper-limit Temperature Input Shift Value
The “input type” parameter must be
set for a thermocouple or resistance
thermometer and the “input shift
type” parameter must be set to a 2-
point shift, or the “input type” param-
eter must be set for an infrared sen-
sor.
insl Lower-limit Temperature Input Shift Value
Setting range Unit Default
199.9 to 999.9 °C or °F0.0
Function
Setting
See
See