EasyManuals Logo

Omron E5CZ User Manual

Omron E5CZ
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
129
Advanced Function Setting Level Section 5-7
5-7 Advanced Function Setting Level
The advanced function setting level is used for optimizing Controller perfor-
mance. To move to this level, input the password (169”) from the initial set-
ting level.
To be able to enter the password, the “initial setting/communications protect”
parameter in the protect level must be set to 0.
The parameters in this level can be used when the “initial setting/commu-
nications protect” parameter is set to 0.
To switch between setting levels, press the O key.
To change set values, press the U and D keys.
Password input
set value 169
Control in progres
s
Control stopped
Operation
Level
Initial Setting
Level
Control stops.
Communi-
cations
Setting
Level
Adjustment
Level
Power ON
Advanced Function
Setting Level
25
100
C
Press the O Key
for at least 1 s.
Press the
O Key less than 1 s.
Press the
O Key
for at
least 3 s.
Press the O Key for at
least 3 s.
Press the
O Key for less than 1 s.
Press the O Key
for at least 1 s.

Table of Contents

Other manuals for Omron E5CZ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CZ and is the answer not in the manual?

Omron E5CZ Specifications

General IconGeneral
Display Type7-segment digital display
Dimensions48 x 48 x 78 mm
Number of Control Outputs1
Ambient Operating Temperature-10 to 55°C
Control MethodPID control, ON/OFF control
Input TypeThermocouple, RTD
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Alarm Output1 or 2 (depending on model)
Setting Resolution0.1 or 1 (depending on input type)
Protection RatingIP20
Ambient Operating Humidity25% to 85% RH (non-condensing)

Related product manuals