115
Adjustment Level Section 5-4
For heating/cooling control, the hysteresis can be set independently for
heating/cooling. The “hysteresis (heating)” parameter is used for the heat-
ing side, and the “hysteresis (cooling)” parameter is used for the cooling
side.
Note Set “none” as the unit for Controllers with Analog Inputs.
Related Parameters
PID ON/OFF:Page 122, Standard or heating/cooling: Page 123 (initial setting
level)
Parameters Model Setting range Unit Default
Hysteresis
(heating)
Controllers with Thermocouple/Resistance
Thermometer Universal-inputs
0.1 to 999.9 °C or °F
(See note.)
1.0
Controllers with Analog Inputs 0.01 to 99.99 %FS 0.10
Hysteresis
(cooling)
Controllers with Thermocouple/Resistance
Thermometer Universal-inputs
0.1 to 999.9 °C or °F
(See note.)
1.0
Controllers with Analog Inputs 0.01 o 99.99 %FS 0.10
See
See
Setting