Advanced Function Setting Level Section 5-7
Alarm 1, 2, or 3 outputs are prevented from turning OFF until after the delay
times set in these parameters have elapsed.
Set the time for which the OFF delay is to be enabled.
To disable the OFF delay, set 0.
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 124 to 126
This parameter sets the shift method for thermocouple or resistance ther-
mometer inputs.
When the input type is thermocouple or resistance thermometer, set
either a 1-point shift or a 2-point shift.
Related Parameters
Temperature input shift: Page 111, Upper-limit temperature input shift value,
Lower-limit temperature input shift value: Page 112 (adjustment level)
Inp
ut type (initial setting level): Page 119
a1of Alarm 1 OFF Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
a2of Alarm 2 OFF Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3of Alarm 3 OFF Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range Unit Default
0 to 999 Second 0
Function
Setting
See
See
istp Input Shift Type
The input type must be thermocou-
ple or resistance thermometer.
Setting range Default
ins1: 1-point shift, ins2: 2-point shift ins1
Function
Setting
See
See