4 - 23
4 Basic Operation
E5@C Digital Temperature Controllers User’s Manual (H174)
4-8 Using ON/OFF Control (Not Supported for Position-proportional
Models.)
4
4-8-2 Settings
Setting the Hysteresis
Set the hysteresis to 2.0°C.
Operating Procedure
1
Press the M Key several times in the Adjustment Level to
display hys (Hysteresis (Heating)).
Adjustment Level
2
Press the U or D Key to set the hysteresis to 2.0.
The default is 1.0.
The new set value can be saved by pressing the M Key, or it will go
into effect after 3 seconds has elapsed.
1.0
hys
Hysteresis
(Heating)
2.0
hys

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20