A-7 Sensor Input Setting Range, Indication Range, Control Range
A
A-7 Sensor Input Setting Range,
Indication Range, Control Range
The default is 5.
The applicable standards for each of the above input ranges are as follows:
K, J, T, E, N, R, S, B: JIS C1602-2015, IEC60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
C/W: W5Re/W26Re, JIS C 1602-2015, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 60751
PLII: According to Platinel II Electromotive Force Table by Engelhard Corp.
* The 0 to 50 mV range can be used only for E5CC-U Digital Controllers and only if they are manufactured in May 2014 or
later (version 2.2 or higher).
Specificati
ons
Set
value
Input setting range Input indication range
Resistance
thermometer
Pt100 0 200 to 850 (°C)/300 to 1500 (°F) 220
to
870 (°C)/340 to 1540 (°F)
1 199.9 to 500.0 (°C)/199.9 to 900.0 (°F) 199.9
to
520.0 (°C)/199.9
to
940.0 (°F)
2 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) 20.0
to
120.0 (°C)/40.0
to
250.0 (°F)
JPt100 3 199.9 to 500.0 (°C)/199.9 to 900.0 (°F) 199.9
to
520.0 (°C)/199.9
to
940.0 (°F)
4 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) 20.0
to
120.0 (°C)/40.0
to
250.0 (°F)
Thermocouple K
5 200 to 1300 (°C)/300 to 2300 (°F) 220
to
1320 (°C)/340
to
2340 (°F)
6 20.0 to 500.0 (°C)/0.0 to 900.0 (°F) 40.0
to
520.0 (°C)/40.0
to
940.0 (°F)
J7100 to 850 (°C)/100 to 1500 (°F) 120
to
870 (°C)/140
to
1540 (°F)
8 20.0 to 400.0 (°C)/0.0 to 750.0 (°F) 40.0
to
420.0 (°C)/40.0
to
790.0 (°F)
T9200 to 400 (°C)/300 to 700 (°F) 220
to
420 (°C)/340
to
740 (°F)
10 199.9 to 400.0 (°C)/199.9 to 700.0 (°F) 199.9
to
420.0 (°C)/199.9
to
740.0 (°F)
E11200 to 600 (°C)/300 to 1100 (°F) 220
to
620 (°C)/340
to
1140 (°F)
L12100 to 850 (°C)/100 to 1500 (°F) 120
to
870 (°C)/140
to
1540 (°F)
U13200 to 400 (°C)/300 to 700 (°F) 220
to
420 (°C)/340
to
740 (°F)
14 199.9 to 400.0 (°C)/199.9 to 700.0 (°F) 199.9
to
420.0 (°C)/199.9
to
740 (°F)
N15200 to 1300 (°C)/300 to 2300 (°F) 220
to
1320 (°C)/340
to
2340 (°F)
R 16 0 to 1700 (°C)/0 to 3000 (°F) 20
to
1720 (°C)/40
to
3040 (°F)
S 17 0 to 1700 (°C)/0 to 3000 (°F) 20
to
1720 (°C)/40
to
3040 (°F)
B 18 0 to 1800 (°C)/0 to 3200 (°F) 20
to
1820 (°C)/40
to
3240 (°F)
C/W 19 0 to 2300 (°C)/0 to 3200 (°F) 20
to
2320 (°C)/40
to
3240 (°F)
PLII 20 0 to 1300 (°C)/0 to 2300 (°F) 20
to
1320 (°C)/40
to
2340 (°F)
ES1B Infrared
Temperature
Sensor
10 to 70°C 21 0 to 90 (°C)/0 to 190 (°F) 20
to
130 (°C)/40
to
270 (°F)
60 to
120°C
22 0 to 120 (°C)/0 to 240 (°F) 20
to
160 (°C)/40
to
320 (°F)
115 to
165°C
23 0 to 165 (°C)/0 to 320 (°F) 20
to
205 (°C)/40 to 400 (°F)
140 to
260°C
24 0 to 260 (°C)/0 to 500 (°F) 20
to
300 (°C)/40 to 580 (°F)
Current input 4 to 20 mA 25 Any of the following ranges, by scaling:
1999 to 9999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
5% to 105% of setting range. The display shows
1999 to 9999 (numeric range with decimal point
omitted).
0 to 20 mA 26
Voltage input 1 to 5 V 27
0 to 5 V 28
0 to 10 V 29
0 to 50 mV 30*

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals