EasyManuals Logo

Omron E5EC User Manual

Omron E5EC
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #247 background imageLoading...
Page #247 background image
5 - 53
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-17 Setting the Width of MV Variation
5
5-17-1 MV Change Rate Limit
5-17 Setting the Width of MV Variation
5-17-1 MV Change Rate Limit
MV Change Rate
Limit
The MV change rate limit sets the maximum allowable width of change per
second in the MV (or the change per second in the valve opening for a
Position-proportional Model). If the change in the MV exceeds this setting, the
MV will be changed by the MV change rate limit until the calculated value is
reached. This function is disabled when the setting is 0.0.
The MV change rate limit does not function in the following situations:
In Manual Mode
During ST execution (Cannot be set when ST is ON.)
During AT execution
During ON/OFF control
While stopped (during MV at Stop output)
During MV at PV Error output
Parameter name Setting range Unit Default Level
MV Change Rate Limit 0.0 to 100.0 %/s 0.0 Adjustment Level
000
0.0
orl

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals