4 Basic Operation
4 - 30
E5@C Digital Temperature Controllers User’s Manual (H174)
Individual PID constants can be manually set in the Proportional Band, Integral Time, and Derivative
Time parameters in the Adjustment Level.
Additional Information
Proportional Action
When PID constants I (integral time) and D (derivative time) are set to 0, control is executed
according to proportional action. As the default, the center value of the proportional band
becomes the set point.
Related parameter: Manual Reset Value (Adjustment Level)
4-9-4 Manual Setup
In this example, the Proportional Band parameter is set to 10.0, the Inte-
gral Time parameter to 250, and the Derivative Time parameter to 45.
Operating Procedure
Setting the Proportional Band
1
Press the M Key several times in the Adjustment Level to
display the p (Proportional Band) parameter.
Adjustment Level
2
Press the U or D Key to set the value to 10.0.
The default settings are as follows:
Temperature input (°C or °F): 8.0
Analog input (%FS): 10.0
Setting the Integral Time
1
Press the M Key several times in the Adjustment Level to
display the i (Integral Time) parameter.
Adjustment Level
2
Press the U or D Key to set the value to 250.
The default settings are as follows:
Integral/Derivative Time Unit of 1 s: 233
Integral/Derivative Time Unit of 0.1 s: 233.0
Setting the Derivative Time
1
Press the M Key several times in the Adjustment Level to
display the d (Derivative Time) parameter.
Adjustment Level
2
Press the U or D Key to set the value to 45.
The default settings are as follows:
Integral/Derivative Time Unit of 1 s: 40
Integral/Derivative Time Unit of 0.1 s: 40.0
8.0
p
Proportional
Band
10.0
p
233
i
Integral Time
250
i
40
d
Derivative Time
45
d

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals