5 - 27
5 Advanced Operations
E5@C Digital Temperature Controllers User’s Manual (H174)
5-10 Alarm Delays
5
5-10-1 Alarm Delays
Use the following procedure to set ON and OFF delays for the alarm 1.
An ON delay of 5 seconds and an OFF delay of 10 s will be set.
Operating Procedure
Setting the Alarm 1 ON Delay
1
Press the M Key several times in the Advanced Function Set-
ting Level to display a1on (Alarm 1 ON Delay).
Advanced Function Setting
Level
2
Press the U or D Key to set the value to 5.
The default is 0.
Setting the Alarm 1 OFF Delay
1
Press the M Key several times in the Advanced Function Set-
ting Level to display a1of (Alarm 1 OFF Delay).
Advanced Function Setting
Level
2
Press the U or D Key to set the value to 10.
The default is 0.
0
a1on
Alarm 1 ON
Delay
5
a1on
0
a1of
Alarm 1 OFF
Delay
10
a1of

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals