6 - 53
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-7 Initial Setting Level
6
o1st
Control Output 1 Signal Control output 1 must be a linear current output.
o2st
Control Output 2 Signal
Control output 2 must be a linear current output.
These parameters set the output signal for linear current outputs.
Select 4 to 20 mA or 0 to 20 mA for the signal.
trst
Transfer Output Signal
There must be a transfer output.
This parameter sets the output signal for the transfer output.
Select 4 to 20 mA or 1 to 5 V.
000
Function
Setting
Setting range Default
4-20: 4 to 20mA
0-20: 0 to 20mA
4-20
000
Function
Setting
Setting range Default
4-20: 4 to 20mA
1-5v: 1 to 5 V
4-20