6 Parameters
6 - 76
E5@C Digital Temperature Controllers User’s Manual (H174)
mani
Manual MV Initial Value
Control must be set to 2-PID control.
A Position-proportional Model set to Close Control
with the Direct Setting of Position-proportional MV
parameter set to ON must be used.
This parameter sets the initial value of the manual MV to use after control moves from Auto-
matic Mode to Manual Mode.
If the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV
lower limit to the MV upper limit.
Related Parameters
Manual Output Method (Advanced Function Setting Level): Page 6-75
Manual MV Limit Enable (Advanced Function Setting Level): Page 6-88
Function
Setting
Setting range Unit Default
Standard control: 5.0 to 105.0 % 0.0
Heating/cooling control: 105.0 to 105.0
See
See

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals