2 - 51
2 Preparations
E5@C Digital Temperature Controllers User’s Manual (H174)
2-2 Using the Terminals
2
2-2-7 E5DC-B Terminal Block Wiring Example
Model Numbers
The input power supply specification of the E5DC-B is given in the following location in the model number.
Terminal Details
Model Numbers
The options specification of the E5DC-B is given in the following location in the model number.
Terminal Details
Do not connect anything to the terminals that are shaded gray.
Note: Use a non-voltage input for the event input.
The polarity for a non-contact input is indicated by “(-).”
Input power supply
Code Specifications Power consumption
A 100 to 240 VAC (50/60 Hz) 4.9 VA max.
D 24 VAC (50/60 Hz)
24 VDC (no polarity)
2.8 VA max./1.5 W max.
100 to 240 VAC 24 VAC/DC
Options
Code Specifications
000 None
002 Communications (RS-485)
and CT1
015 Communications (RS-485)
002 015
E5DC-@@@@BM-@@@
Input power supply
B
A
(no polarity)
B
A
E5DC-@@@@BM-@@@
Option
B(+)
A(-)
RS-485
Communications
CT1
CT
G
H
E
F
B(+)
A(-)
RS-485
Communications
G
H
E
F

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20