EasyManua.ls Logo

Omron NE1A-EDR01 - Troubleshooting; ED Router Errors and Error Processing

Omron NE1A-EDR01
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
Troubleshooting Section 3-2
3-2 Troubleshooting
3-2-1 ED Router Errors and Error Processing
Indicators/Display Error Cause ED Router
operation
Error
code
(hex)
Countermeasures
MS NS D NS E 7-seg-
ment
Hardware-related Errors
Lit red Not lit Not lit Not lit
or H3
System error ED Router fail-
ure
Operation stops. None
or
0601
Replace the ED Router if the
problem recurs after restart-
ing.
Flash-
ing
red
--- --- E9 Memory
access error
An error
occurred in
involatile mem-
ory in the Unit.
Operation stops. 0602
Flash-
ing
red
--- Not lit F4 Ethernet
communica-
tions control-
ler error
An Ethernet
communications
controller error
occurred.
Ethernet commu-
nications stop.
020F
Communications-related Error
--- --- --- --- Illegal mes-
sage dis-
carded.
The message
was discarded
due to illegal
packet commu-
nications.
Operation stops. 0118 Check the system communi-
cations status.
Ethernet Communications-related Errors
--- --- --- E1 Link OFF
error
No link was
detected
between switch-
ing hubs.
Operation contin-
ues after error
recovery.
03D3 Check the Ethernet cable,
hub, etc.
--- --- Not lit E3 Server con-
nection error
An error
occurred
between the ED
Router and the
BOOTP server.
There is no
response from
the BOOTP
server.
The IP address
received from
the BOOTP
server is illegal.
Ethernet commu-
nications stop until
a legal IP address
can be received.
03C4 Check the BOOTP server.
--- --- Lit red F0 IP address
duplication
error
The ED Router
IP address is the
same as the IP
address set for
another device.
Ethernet commu-
nications stop.
0211 Check the IP address set-
tings and the network con-
nections.

Table of Contents