DST1 Series Monitoring Section 4-7
Read Data Format (Read Size: 1 Byte)
Error Cause
(3) Instance ID
Status held in the DST1-ID12SL-1 can be monitored by reading the in-
stance IDs shown in the following table.
Data (status) indicated by a black dot (● ) can be read.
I/O Assembly Data
Format
Instance ID: 20C
Monitor value: 1: ON, 0: OFF
Instance ID: 224
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
+0 Error cause
Value Meaning
0 No error
1 Illegal configuration
2 Test signal error
3 Internal circuit error
4 Discrepancy error
5 Error at dual channel partner
Instance
ID (hex)
Safety
input
Safety
input
batch
status
Safety
input
status
Safety
output
batch
status
Safety
output
status
Muting
lamp
status
Safety
output
monitor
Test
output
status
Overall
status
20C ●
224 ●●
22C ●●
300 ●
310 ●● ●
311 ●● ●
312 ●● ●●
340 ●●
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1 Reserved Safety input
terminal No.
11 monitor
Safety input
terminal No.
10 monitor
Safety input
terminal No.
9 monitor
Safety input
terminal No.
8 monitor
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1 Safety input
terminal No.
7 status
Safety input
terminal No.
6 status
Safety input
terminal No.
5 status
Safety input
terminal No.
4 status
Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status