75
DST1 Series Monitoring Section 4-7
Data (status) indicated by a black dot (●) can be read.
I/O Assembly Data
Format
Status ID: 203
Monitor value: 1: ON, 0: OFF
Instance ID: 300
For details on overall status, refer to 4-7-3 Monitoring the DST1-MRD08SL-1.
Instance ID: 330
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
Instance ID: 331
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
Instance ID: 332
Monitor value: 1: ON, 0: OFF Status value: 1: Normal, 0: Error
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Reserved Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Overall status
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Muting
lamp status
Safety input
batch status
Safety out-
put batch
status
Reserved Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1 Muting
lamp status
Reserved Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
Offset
(bytes)
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
+0 Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1 Safety out-
put termi-
nal No. 3
monitor
Safety out-
put termi-
nal No. 2
monitor
Safety out-
put termi-
nal No. 1
monitor
Safety out-
put termi-
nal No. 0
monitor
Safety out-
put termi-
nal No. 3
status
Safety out-
put termi-
nal No. 2
status
Safety out-
put termi-
nal No. 1
status
Safety out-
put termi-
nal No. 0
status
+2 Muting
lamp status
Reserved