26
4. UPS functions
UPS stop signal setting (BS) (setting switch 7 )
Factory setting: OFF
OFF: The BS signal is always valid (raceivable).
The unit’s “power output” can be stopped by inputting a “ON” backup power supply stop signal
(BS) that continues for 10 seconds or more..
ON: The BS signal is valid (raceivable) only when in Battery Mode.(The signal is not received when in
Commercial Power Mode.)
The unit’s “power output” can be stopped by inputting a “ON” backup power supply stop signal (BS)
that continues for 0.01(10ms) seconds or more.
Use this setting in commercial operation when you do not want to stop operations when a backup
power supply stop signal (BS) is received
.
15A/20A plug setting (setting switch 8 )
Factory setting: OFF (BU150SW only)
OFF: Set to OFF when using a 15A AC input plug. The UPS can connect to as much as the “rated out-
put capacity (1100VA/950W)” for a 15A plug.
ON: Set to ON when using a 20A AC input plug. The UPS can connect to as much as the “rated out-
put capacity (1500VA/1050W)” for a 20A plug.
* Valid only when using contact signal interface.
1 2 53 4 86 7
ON DIP
1 2 53 4 86 7
ON DIP
ON
OFF
ON
OFF
ON
AC input
BS signal
UPS output
OFF
Shutdown delay timing
This delay corresponds to the settings
for switch 5 and switch 6 .
This timing is 10 ms or 10 sec.
Timing corresponds to the settings
for switch 7 .
The UPS delays the shutdown timing.
If the user sets “switch 5: ON, switch 6: ON”, the UPS does not stop the output, even if the backup power
supply stop signal (BS) is valid.
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is “High”, the UPS stops the output immediately.