BU50SW / BU75SW / BU100SW / BU150SW
57
1
2
3
4
5
6
7
8
9
10
BU50SW BU75SW BU100SW BU150SW
Method Operation method
Full-time inverter supply method
Connectable devices
PC, display, and peripherals
Input
Nominal Input voltage 100/110/115/120 VAC
Input voltage range
75p4 to 144p4V AC (with 90% or less connection load)
85p4 to 144p4V AC (with 90% or less connection load)
500VA/350W 750VA/500W 1000VA/700W 1500VA/1050W
100V mode 100V AC
p3%
110V mode 110V AC
p3%
115V mode 115V AC
p3%
120V mode 120V AC
p3%
Input frequency 50/60Hz p 4Hz
Maximum current 8A 10A 12A 16A
Phase Single-phase, two-wire
Input plug shape 3P (NEMA 5-15P)
3P (NEMA 5-15P/L5-20P)
Input protection Reset-type overcurrent protection device
Input protection capacity
10A 10A 15A 20A
Output
Output capacity
(shared maximum)
*
1
Output voltage *2
Peak voltage value 100V mode: 141V AC p6% 110V mode: 156V AC p6%
(In Commercial Power Mode)
115V mode: 163V AC ア6% 120V mode: 170V AC ア6%
Peak voltage value 100V mode: 141V AC +6/-6% 110V mode: 156V AC+6/-9%
(In Battery Mode)
115V mode: 163V AC +6/-13% 120V mode: 170V AC +6/-17%
Output frequency 50/60Hzp1Hz
Phase Single-phase, two-wire
Output waveform
(
In Commercial Power Mode/
Batttery Mode)
Sine wave / Shine wave
Waveform distortion rate
100V mode: 6% max. 110V mode: 9% max.
(Rectified load, at rated output)
115V mode: 13% max. 120V mode: 17% max.
Output receptacle
NEMA 5-15R
Number of output receptacles
Backup: 6 Backup: 5
Power failure switching time
Uninterrupted
Commercial direct shipment
(switching time)
4 msec. max.
Backup time *3
Minimum 8 minutes Minimum 5 minutes Minimum 5 minutes Minimum 4 minutes
Battery Type Compact sealed lead battery
Sealed lead battery
life expectancy
4 to 5 years (long operating life) *At ambient temperature of 20
。
C
Battery capacity
(V/Ah) (x Quantity)
12V DC/ 7.2 Ah (x 2) 12V DC/ 7.2 Ah (x 3) 12V DC/ 9 Ah (x 3)
Charging time 8 hours 8 hours *4
Environment Operating ambient
temperature
0 to 40
。
C (during operation)/ -15 to 50
。
C (during storage)
Operating ambient
humidity
25 to 85%RH (during use)/10 to 90%RH (during storage)
Dimensions
(WxDxHmm)
145 x 395 x 224 *5 145 x 480 x 224 *5
Weight of unit
Approx. 13 kg Approx. 13 kg Approx. 15.5 kg Approx. 16.5 kg
Internal power
consumption (max.)
45W (65W max.)
50W (70W max.) 55W (80W max.)
Noise regulation
(compliance standard)
VCCI Class A
Safety standard compliance
/RoHS directive compliance
UL1778 / CE / RoHS compliance
Noise 50 dB max.
*1: Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the
range specifi ed here.
*2: Check the operation beforehand if the unit is used in any mode other than “100V AC mode”. In some cases,
the maximum voltage of output in Battery Mode may be lower than the maximum voltage in usual operation
(commercial power supply).
*3: The backup times shown here are for when rated load is connected, at 20
°
C, and for initial characteristics.
*4: When an additional battery unit is connected, the charging time is 24 hours.
*5: The height includes the 13-mm height of the rubber feet.
Reference
A. Specifi cations