BU75RW/BU100RW/BU200RW/BU300RW
2
19
Caution
BU300RW connection procedure
●
When using the 30A plug (connected when shipped)
Provide a wall outlet (commercial power) compatible with the shape of the 30A plug (NEMA L5-30P).
●
The BU300RW comes equipped with a 30A input plug (NEMA L5-30P) at shipment.
If this plug is used, make sure that the capacity of the connected devices stays below the maximum
capacities shown in the table above.
●
After connecting to commercial power, turn ON the INPUT PROTECTION switch (input overcurrent
protection switch) on the back of the unit.
●
When the overload display appears (“ “ or “ “ is displayed on the status indicator), you must con-
nect to a power switchboard or switch to a 30A plug. Follow the directions provided in the “Changing
the AC input cable” section below.
When using the 30A plug (NEMAL5-30P) with the BU300RW, the
maximum capacity connectable to the output is approximately
2400VA/1920W.
●
When the power consumption exceeds this capacity, the input voltage becomes larger than
30A, which may lead to overheating or fi re.
●
When the overload display appears (“ “ or “ “ is displayed on the status indicator), you
must change the AC input cable and connect to a commercial power line with a capacity of
35A or more. Follow the directions provided in the “Changing the AC input cable” section be-
low.
Caution
When using the 15A plug (NEMA 5-15P) with the BU200RW, the
maximum capacity connectable to the output is approximately
1100VA/880W.
●
When the power consumption exceeds this capacity, the input voltage becomes larger than
15A, which may lead to overheating or fi re.
●
When the overload display appears (“ “ or “ “ is displayed on the status indicator), you
must switch to a 30A plug. Follow the directions provided in the “Changing the AC input cable”
section below.
<BU75RW/BU100RW>
P C
3P receptacle
2P receptacle
Connect the grounding wire to earth in building