3.Operation
26
Explanation
Usual operation
You may either leave the power switch of the unit ON (operation status) or turn it OFF each time when
stopping the connected system. Choose whichever operation method is more convenient. We recom-
mend turning OFF the power switch when you do not use connected devices for a long time.
BU75RW/BU100RW: The battery can be charged once the AC input plug of the unit is connected to a wall
outlet (commercial power).
BU200RW/BU300RW: The battery can be charged once the AC input plug is connected to a wall outlet
(commercial power) and the INPUT PROTECTION switch (input overcurrent protection switch) on the
back of the unit is turned ON.
Quitting Battery Mode
If a power failure lasts for an extended period of time, the battery discharges and power output from the
unit stops. Shut down your computer after performing appropriate procedures (for example, saving data)
while the unit is still supplying power.
Rebooting
If the battery discharges completely during a power failure, the unit stops. After recovery from the power
failure, the unit automatically restarts and supplies power. If you do not want to restart the connected de-
vices, turn OFF the power switch of either the unit or the connected devices.
See also
Setting switch
󱦱
can be used to select whether or not auto restart is performed. See Page 35
Scheduled operation using the UPS monitoring software
When performing scheduled operation in which the UPS is stopped and a device such as a breaker is
used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3
months for the start of the next operation. If you specify a period longer than 3 months, the internal timer
is reset and the scheduled operation does not start.
Note that this period reduces to less than half when the battery is at the end of its life.
If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing the
Start Switch. However, if the battery is deteriorated, you may not be able to start operation. In this case,
replace the battery according to the instructions in “6-2 Replacing the battery” on page 46.
Notes
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery
Mode, the battery life may be signi cantly shortened.
Take measures for handling unforeseen accidents, such as data backup
and system redundancy.
The output may stop when there is a circuit failure in the UPS.