4. UPS functions
38
●
AC input plug selection (setting switch
,
)
…
Factory setting: Refer to the table below.
Setting switch
Setting switch
BU75RW BU100RW BU200RW BU300RW
OFF OFF
15A
Factory setting
15A
Factory setting
15A
Factory setting
15A
ON OFF - - 20A 20A
OFF ON - -
30A or power
switchboard con-
nection
30A
Factory setting
ON ON - - -
35A or greater power
switchboard connection
BU75RW
Use the factory settings for 7 and 8 (both OFF). The UPS can be connected to a rated output
capacity as high as 750VA/600W (factory settings).
BU100RW
Use the factory settings for 7 and 8 (both OFF). The UPS can be connected to a rated output
capacity as high as 1000VA/800W (factory settings).
BU200RW
OFF,
OFF: Use this setting when using the 15A AC plug that is connected at shipment. The
UPS can be connected to a rated output capacity as high as 1100VA/880W (fac-
tory settings).
ON,
OFF: Use this setting when changing to a 20A AC input plug. The UPS can be con-
nected to a rated output capacity as high as 1600VA/1280W.
OFF,
ON: Use this setting when changing to a 30A AC input plug or power switchboard
connection.
The UPS can be connected to a rated output capacity as high as 2000VA/1600W.
BU300RW
OFF,
OFF: Use this setting when changing to a 15A AC input plug. The UPS can be
connected to a rated output capacity as high as 1100VA/880W.
ON,
OFF: Use this setting when changing to a 20A AC input plug. The UPS can be
connected to a rated output capacity as high as 1600VA/1280W.
OFF,
ON: Use this setting when using the 30A AC input plug that is connected at
shipment. The UPS can be connected to a rated output capacity as high as
2400VA/1920W. (Factory settings)
ON,
ON: Use this setting when changing to an AC input plug that is connected to a
power switchboard. The UPS can be connected to a rated output capacity as
high as 3000VA/2400W.
1 2 53 4 86 7
ON DIP