5. Measuring the backup time
44
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from
the graph below.
●
Graph of backup time (graph of initial values for products that have not been used at 20°C)
The backup time becomes shorter than the graph (table) below when temperature is lower.
●
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
* These backup times are for reference only. Times may vary according to battery life and external
environmental conditions (temperature, etc.).
200W 400W 600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2200W 2400W
BU300RW 80 40 26 18 14 11 9 7 6 5.3 4.5 4
BU300RW +
BUM300R
240 150 100 75 55 44 35 30 26 23 20 18
Model
Connection capacity (Watts)
Time unit : Minutes
Backuptimetable
Timeunit:(Minutes)
Model
Connection capacity (Watts)
20W 50W 100W 200W 300W 400W 500W 600W
BU75RW 250 150 85 36 23 18 13 10
BU75RW +
BUM100R
860 520 320 170 100 75 50 44
Model
Connection capacity (Watts)
20W 50W 100W 200W 300W 400W 500W 600W 700W 800W
BU100RW 250 150 85 36 23 18 13 10 8.5 7
BU100RW +
BUM100R
860 520 320 170 100 75 50 44 36 31
Model
Connection capacity (Watts)
100W 200W 400W 600W 800W 1000W 1200W 1400W 1600W
BU200RW 150 80 40 26 18 14 11 9 7
BU200RW +
BUM300R
500 240 150 100 75 55 44 35 30