5. Measuring the backup time
44
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from
the graph below.
Graph of backup time (graph of initial values for products that have not been used at 20°C)
The backup time becomes shorter than the graph (table) below when temperature is lower.
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
Backup time (Minutes)
Power consumption
of connected devices (W)
2400230022002100200019001800170016001500140013001200110010009008007006005004003002001000
BU200RW
BU300RW
0
10
20
30
40
50
60
70
80
90
100
110
120
BU100RW +
BUM100R
BU75RW +
BUM100R
BU300RW +
BUM300R
BU200RW +
BUM300R
BU75RW
BU100RW
Backup time
(20°C, initial value)
* These backup times are for reference only. Times may vary according to battery life and external
environmental conditions (temperature, etc.).
200W 400W 600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2200W 2400W
BU300RW 80 40 26 18 14 11 9 7 6 5.3 4.5 4
BU300RW +
BUM300R
240 150 100 75 55 44 35 30 26 23 20 18
Model
Connection capacity (Watts)
Time unit : Minutes
Backuptimetable
Timeunit:(Minutes)
Model
Connection capacity (Watts)
20W 50W 100W 200W 300W 400W 500W 600W
BU75RW 250 150 85 36 23 18 13 10
BU75RW +
BUM100R
860 520 320 170 100 75 50 44

Model
Connection capacity (Watts)
20W 50W 100W 200W 300W 400W 500W 600W 700W 800W
BU100RW 250 150 85 36 23 18 13 10 8.5 7
BU100RW +
BUM100R
860 520 320 170 100 75 50 44 36 31

Model
Connection capacity (Watts)
100W 200W 400W 600W 800W 1000W 1200W 1400W 1600W
BU200RW 150 80 40 26 18 14 11 9 7
BU200RW +
BUM300R
500 240 150 100 75 55 44 35 30