6. Maintenance and Inspection
56
Replacement fan
For BU75RW/BU100RW rear: Model BUF100R
For BU200RW/BU300RW rear: Model BUF300RF
For BU200RW/BU300RW front: Model BUF300FF
■
Fan replacement procedure
1.
Use a screwdriver to loosen (turn counter-clockwise) and remove the cooling fan screws 4 screws.
(The diagram shows the BU200RW/BU300RW rear cooling fan.)
Fan replacement is complete.
4.
Insert the fan into the unit’s fan recess.
Use the screwdriver to securely tighten (turn clockwise) the removed screws (4 screws for rear
fan, front fan).
When doing so, make sure the cable does not become pinned under the fan cover.
3.
Insert the new fan connector until it clicks into place.
The beep stops, and the "EF" status display lamp turns OFF.
2.
While pressing down on the tip of the fan connector
, pull it toward
you to disconnect it.
The beep stops, and the error lamp turns OFF.
Loosen the 4 Phillips-type screws.
1
2
3
2