BU75RW/BU100RW/BU200RW/BU300RW
7
73
7-4-4. Contact Signal Connector (female DSUB9P)
■
Insert/ removal method of contact signal card
(1) Turn OFF the power switch, turn OFF the INPUT PROTECTION switch (input overcurrent protec-
tion switch), remove the top and bottom screws (2 screws) of the contact signal card on the back
of the unit, and carefully remove the contact signal card.
(2) After changing the settings, carefully reinsert the contact signal card and securely tighten the 2
screws.
Pin assignment
Pin number
For jumper setting “SC07”
* Factory settings
For jumper setting “SC05/06”
5 4 3 2 1
9 8 7 6
Front view
Screw size: inch screw
#4-40 UNC
1 Battery LOW signal output (BL) NC
2 Trouble signal output (TR) Backup signal output (BU)
3 Backup stop signal input (BS)
Backup reverse signal output
(BU)
4 NC COMMON (COM)
5 COMMON (COM)
Battery Low Signal output
(BL)
6 Remote ON/OFF input (-) Backup stop signal input (BS)
7 Remote ON/OFF input (+) Remote ON/OFF input (-)
8 Backup signal output (BU) Trouble Signal output (TR)
9
Battery replacement signal output (WB)
Remote ON/OFF input (+)
BU200RW/BU300RW
BU200RW/BU300RW
BU75RW/BU100RW
BU75RW/BU100RW