22
Setting the DIP Switch The operation of High-density I/O Units is controlled by setting the pins of the
DIP switch on the back panel. The following table shows the function of each pin
and applicable Units.
Pin Function Applicable Units
Setting
ON OFF
1 Operating mode C200H-OD501/OD215 128 dynamic outputs 32 outputs
C200H-MD501/MD115/MD215 128 dynamic inputs 16 inputs, 16 outputs
2 High-speed input
1
C200H-ID501/ID215 Inputs 08 to 15 of CN2
are high-speed inputs.
Normal inputs
C200H-MD501/MD115/MD215 Inputs 08 to 15 of CN2
are high-speed inputs.
Normal inputs
3 High-speed input
minimum pulse width
2
C200H-ID501/ID215
C200H-MD501/MD115/MD215
4 ms 1 ms
4 Input response time
3
C200H-ID501/ID215
C200H-MD501/MD115/MD215
15 ms max. 2.5 ms max.
5 Data output mode
4
C200H-OD501/OD215 Positive logic Negative logic
6 Not used. --- --- ---
Note 1. Used in the C200H-MD501/MD115/MD215 only when pin 1 is OFF, setting
the Unit to static mode.
2. Used in the C200H-ID501/215, C200H-MD501/MD215/MD115/MD215
only when pin 2 is ON, setting the Unit to High-speed input mode.
3. Sets the input response time for normal inputs. When pin 2 is ON, CN2 08 to
15 are pulse-catch inputs. Other inputs can be used as normal inputs.
4. Used when pin 1 is ON, setting the C200H-OD501/OD215 to dynamic out-
put mode.
I/O Unit locking notch
Nameplate
I/O indicators:
Indicate ON/OFF status of points
24-pin connectors
Unit number setting switch
I/O Units Section 2-5