42
Current Supplied
Name Model number Max. current supplied (See note 1) Maximum
5 V
(internal logic
current)
26 V
(relay current)
24 V
(No-voltage
contact current)
power
CPU Rack C200H-CPU21-E 3.2 A 0.6 A 0.8 A 20 to 23 W
(See note 2)
C200H-CPU23-E 1.6 A 0.6 A --- 18 W
C200H-CPU31-E 3.0 A 0.6 A 0.8 A 19 to 22 W
(See note 2)
Expansion
C200H-PS221 2.7 A 0.6 A 0.8 A 28 W
I/O Rack
C200H-PS211 --- 23 W
Slave Rack C200H-RT001-P 2.7 A 0.6 A 0.8 A 28 W
C200H-RT002-P --- 23 W
C200H-RT201 0.8 A 28 W
C200H-RT202 --- 23 W
Note 1. The figures shown in the “maximum current supplied” and “maximum power
supplied” columns are computed with the power consumed by the Back-
planes, CPU Unit, Memory Cassettes, Peripheral Devices, I/O Power Sup-
ply Units, and Slave Units already calculated.
Design the system so that the following two conditions are satisfied.
Condition 1
(1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in
the 5-V column)
(2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in
the 26-V column)
(3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in
the 24-V column)
Condition 2
(1) x 5 V + (2) x 26 V + (3) x 24 ≤ (maximum power supplied)
2. In the C200H-CPU21-E and C200H-CPU31-E, the maximum power drawn
from the 5-V supply depends upon the current, as shown below.
Max. Power vs. Current Supplied
Total Power Consumption (W)
Current Drawn from 5-V Supply (A)
C200H-CPU21-E
Total Power Consumption (W)
Current Drawn from 5-V Supply (A)
C200H-CPU31-E
0 1.6
20
23
3.2
0
(W)
(A)
0 1.4
19
22
3.0
0
(W)
(A)
Maximum Current and Power Supplied Section 4-3
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com