45
Unit Model number Current
consumption
Host Link C200H-LK101-PV1 0.25 A
C200H-LK201-V1 0.15 A
C200H-LK202-V1 0.25 A
PC Link C200H-LK401 0.35 A
Remote Master C200H-RM001-PV1 0.20 A
C200H-RM201 0.25 A
SYSMAC LINK Unit C200HW-SLK13/SLK14/SLK23/
SLK24
0.8 A
SYSMAC NET Link Unit C200HS-SNT32 1.0 A
Feed Adapter C200H-APS01/ASP02/ASP03 0 A
Unit Model number Current
consumption
Contact Output C200H-OC221/OC222/OC223/
OC224/OC225
0.075 A*
Transistor Output C200H-OD216/OD217
ID Sensor C200H-IDS01-V1/IDS21 0.12 A
Note *With all eight outputs ON simultaneously.
Unit Model number Current
consumption
No-Voltage Contact
Input Units
C200H-ID001/ID002 0.06 A
Calculation Examples The total power consumption for each Rack can be obtained from the following
formulas
Total power consumption for each Unit + 7 (8)
0.6 x 0.55 (1)
CPU Rack =
(VA)
7 = CPU Unit power consumption, (8) = Power consumption of the
CPU21-E/23-E
0.6 = 60% efficiency
0.55 (1) = Power rate (Number in parentheses: when CPU31-E is used.)
Total power consumption for each Unit + 2
0.6 x 0.55 (1)
All other Racks =
(VA)
2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption
0.6 = 60% efficiency
0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202
is used.)
Example 1 Assume that four Contact Output Units, three No-Voltage Contact Input Units,
and one Host Link Unit are mounted to a Rack, along with CPU21-E. The follow-
ing table shows how the total power consumption is calculated.
Voltage Current consumption Power consumption
5 V
(1) 0.01 x 7 + 0.25 = 0.32 A (≤ 3.2 A)
(1) x 5 V = 1.6 W
26 V
(2) 0.075 x 4 = 0.30 A (≤ 0.6 A)
(2) x 26 V = 7.8 W
24 V
(3) 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A)
(3) x 24 V = 11.52 W
Total ---
20.92 W (≤ 23 W)
Current Drawn from 5-V
Supply for Other Units
Current Drawn from 26-V
Supply
Current Drawn from 24-V
Supply
Maximum Current and Power Supplied Section 4-3